BUILDING WIRE – COPPER – XHHW

Polytherm Cross-Linked Polyethylene

(XLP) Insulated Copper Conductors
90°C Dry or Wet
600 Volts
1/0 or larger rated for CT use
Sunlight Resistant
Gasoline and Oil Resistant I & II

APPLICATIONS

• For use in conduit or other recognized raceways for service, feeder, and branch circuit applications as specified in the NEC®
• Good choice for industrial applications where better insulation toughness and resistance to moisture and heat is desired
• For use in wet or dry locations at temperatures up to 90°C
• Sunlight resistant

CONDUCTORS

• Stranded conductors: Uncoated, soft copper per ASTM-B8 (2 AWG 
  and 250 MCM – 750 MCM), and ASTM-B787 (1 AWG – 4/0)

INSULATION
• XLP (cross-linked polyethylene)

INDUSTRY STANDARDS

• UL 44
•CSA LL 82214
• ASTM-B3
• ASTM-B8
• ASTM-B787
• Federal Specification A-A-59544
• NFPA70: National Electrical Code®
• NEMA WC70/ICEA S-95-658

Product Code
Conductors
Insulation Thickness Mils.
Approx. O.D. Inches
Allowable Ampacities*
Approx. Net Wt. lbs./m ft.
AWG Size
No. of Strands
60°C **
75°C ***
90°C ****
117-4000
8
7
45
0.240
40
50
55
65
117-4200
6
7
45
0.280
55
65
75
97
117-4400
4
7
45
0.330
70
85
95
148
117-4500
3
7
45
0.353
-
-
110
180
117-4600
2
7
45
0.390
95
115
130
229
117-4700
1
19
55
0.450
110
130
150
293
117-5000
1/0
19
55
0.489
125
150
170
364
117-5200
2/0
19
55
0.530
145
175
195
449
117-5400
3/0
19
55
0.550
165
200
225
559
117-5600
4/0
19
55
0.640
195
230
260
698
117-6000
250
37
65
0.710
215
255
290
834
117-6400
300
37
65
0.760
-
-
320
995
117-6800
350
37
65
0.820
260
310
350
1152
117-7200
400
37
65
0.860
280
335
380
1309
117-8000
500
37
65
0.950
320
380
430
1622
117-8400
600
61
80
1.040
355
420
475
1947