CONTROL CABLE – TFN, PVC/NYLON

Specification:
HW150
Tray Cable – Control Cable
600 Volt UL Type TC
TFN Insulation
PVC Jacket
Copper Conductor

Catalog Number Size AWG No. of Conductors No. of Strands Nylon Jacket Thickness Mils Insulation Thickness Mils Jacket Thickness Mils Overall Diameter Inch Net Weight Lbs/Mft
HW150 01802* 18 2 7 4 15 45 .19 x .28 33
HW150 01803 18 3 7 4 15 45 0.28 43
HW150 01804 18 4 7 4 15 45 0.31 52
HW150 01805 18 5 7 4 15 45 0.33 62
HW150 01806 18 6 7 4 15 45 0.36 72
HW150 01807 18 7 7 4 15 45 0.37 79
HW150 01808 18 8 7 4 15 45 0.38 89
HW150 01809 18 9 7 4 15 45 0.41 104
HW150 01810 18 10 7 4 15 45 0.45 111
HW150 01812 18 12 7 4 15 45 0.46 127
HW150 01815 18 15 7 4 15 45 0.51 157
HW150 01819 18 19 7 4 15 60 0.57 202
HW150 01825 18 25 7 4 15 60 0.65 258
HW150 01830 18 30 7 4 15 60 0.69 300
HW150 01837 18 37 7 4 15 60 0.74 360
HW150 01602* 16 2 7 4 15 45 .20 x .30 42
HW150 01603 16 3 7 4 15 45 0.31 55
HW150 01604 16 4 7 4 15 45 0.34 69
HW150 01605 16 5 7 4 15 45 0.36 83
HW150 01606 16 6 7 4 15 45 0.39 96
HW150 01607 16 7 7 4 15 45 0.39 106
HW150 01608 16 8 7 4 15 45 0.39 122
HW150 01609 16 9 7 4 15 45 0.43 138
HW150 01610 16 10 7 4 15 45 0.46 149
HW150 01612 16 12 7 4 15 45 0.51 174
HW150 01615 16 15 7 4 15 60 0.60 229
HW150 01616 16 16 7 4 15 60 0.60 241
HW150 01619 16 19 7 4 15 60 0.63 275
HW150 01620 16 20 7 4 15 60 0.66 291
HW150 01625 16 25 7 4 15 60 0.72 355
HW150 01630 16 30 7 4 15 60 0.77 414
HW150 01637 16 37 7 4 15 80 0.82 498
HW150 01650 16 50 7 4 15 80 1.01 703

* Flat Construction

Application:

General purpose cable for use in power, control and lighting circuits in a broad range of commerical and industrial applications. Approved for continuous operation at 90? in dry locations, installation indoorsor outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 hazardous locations.

Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.

Insulation:
Flame-retardent PVC per UL Standard 62 for Type TFN wire.

Insulation Jacket:
Clear nylon per UL Standard 62 for Type TFN wire.

Jacket:
Sunlight-resistant PVC per UL Standard 1277.

Flame Tests:
•IEEE 383 70,000 BTU/hr flame test

Color Code:
ICEA Method 1, Table E-2

Additional Standards:
•UL Type TC per Article 336 of the NEC
•Approved for Class 1 remote-control and signaling circuits per Article 725 of the NEC