CONTROL CABLE – XHHW-2, VW-1, FR-EP, CPE

Specification:
HW158
Tray Cable – Control Cable
600 Volt UL Type TC, 90°C
FR-EP VW-1 XHHW-2 Insulation
CPE Jacket
Tinned Copper Conductors 

Catalog Number Size AWG No. of Conductors No. of Strands Insulation Thickness Mils Jacket Thickness Mils Overall Diameter Inch Net Weight Lbs/Mft
HW158 01402* 14 2 7 30 45 .37 x .23 71
HW158 01403 14 3 7 30 45 0.39 92
HW158 01404 14 4 7 30 45 0.43 115
HW158 01405 14 5 7 30 45 0.47 139
HW158 01407 14 7 7 30 60 0.51 183
HW158 01409 14 9 7 30 60 0.62 250
HW158 01412 14 12 7 30 60 0.70 317
HW158 01415 14 15 7 30 60 0.76 383
HW158 01419 14 19 7 30 60 0.82 468
HW158 01425 14 25 7 30 60 0.99 645
HW158 01430 14 30 7 30 60 1.05 747
HW158 01437 14 37 7 30 60 1.03 897
HW158 01202* 12 2 7 30 45 .40 x .25 94
HW158 01203 12 3 7 30 45 0.44 124
HW158 01204 12 4 7 30 45 0.48 157
HW158 01205 12 5 7 30 60 0.52 191
HW158 01207 12 7 7 30 60 0.60 268
HW158 01209 12 9 7 30 60 0.70 347
HW158 01212 12 12 7 30 60 0.78 437
HW158 01215 12 15 7 30 60 0.88 561
HW158 01219 12 19 7 30 60 0.96 688
HW158 01225 12 25 7 30 60 1.01 894
HW158 01230 12 30 7 30 60 1.18 1040
HW158 01237 12 37 7 30 60 1.27 1256
HW158 01002* 10 2 7 30 45 .45 x .27 128
HW158 01003 10 3 7 30 45 0.49 172
HW158 01004 10 4 7 30 60 0.56 234
HW158 01005 10 5 7 30 60 0.62 284
HW158 01007 10 7 7 30 60 0.67 381
HW158 01009 10 9 7 30 60 0.79 488
HW158 01012 10 12 7 30 60 0.92 651
HW158 01015 10 15 7 30 60 1.02 812
HW158 01019 10 19 7 30 60 1.08 967
HW158 01024 10 24 7 30 60 1.36 1221
HW158 01037 10 37 7 30 60 2.10 1882

* Flat Construction

Application:
Superior flame-retardant cable for use in power, control and lighting circuits in a broad range of commercial and industrial applications where resistance to caustic environments is required. Approved for use in wet or dry locations at 90°C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be installed at temperatures as low as -35°C and used in NEC Class I and II, Division 2 hazardous locations. UL approved for use at 90°C for continuous operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductors:
Tin-coated, soft annealed copper per ASTM B-33, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact).

Insulation:
Flame-retardant ethylene-propylene-rubber (FR-EP) per ICEA S-73-532 and UL Standard 44 for Type XHHW-2, VW-1 conductors.

Jacket:
Sunlight-resistant chlorinated polyethylene (CPE) per ICEA S-73-532 and UL Standard 1277.

Flame Tests:
•IEEE 383 70,000 BTU/hr flame test
•IEEE 1202 70,000 BTU/hr CSA FT4 flame test
•UL Standard 1277 70,000 BTU/hr flame test
•ICEA T-29-520 210,000 BTU/hr flame test
•Individual conductors pass the UL VW-1 flame test

Color Code:
ICEA Method 1, Table E-2

Additional Standards:
•UL Type TC per Article 336 of the NEC.
•Approved for Class 1 remote-control and signaling circuits per Article 725 of the NEC.
•NEMA WC 57