CONTROL CABLE – XLP, XHHW-2, LS-ZH

Specification:
HW170
Tray Cable – Control Cable
600 Volt UL Type TC-LS, 90°C
XLP XHHW-2 Insulation
Low Smoke Zero Halogen
Tinned Copper Conductors
FM Approved

Catalog Number Size AWG Number of Conductors Number of Strands Insulation Thickness Jacket Thickness Overall Diameter Inch Net Weight Lbs/Mft
HW170 01402 14 2 7 30 45 0.36 66
HW170 01403 14 3 7 30 45 0.38 86
HW170 01404 14 4 7 30 45 0.42 108
HW170 01405 14 5 7 30 45 0.45 130
HW170 01407 14 7 7 30 60 0.49 169
HW170 01409 14 9 7 30 60 0.62 238
HW170 01412 14 12 7 30 60 0.69 298
HW170 01419 14 19 7 30 60 0.80 438
HW170 01425 14 25 7 30 60 0.96 631
HW170 01430 14 30 7 30 60 1.04 721
HW170 01437 14 37 7 30 60 1.13 867
HW170 01202 12 2 7 30 45 0.40 87
HW170 01203 12 3 7 30 45 0.42 117
HW170 01204 12 4 7 30 45 0.46 147
HW170 01205 12 5 7 30 60 0.50 178
HW170 01207 12 7 7 30 60 0.58 253
HW170 01209 12 9 7 30 60 0.68 360
HW170 01212 12 12 7 30 60 0.76 409
HW170 01219 12 19 7 30 60 0.93 651
HW170 01225 12 25 7 30 60 1.01 894
HW170 01230 12 30 7 30 60 1.18 1040
HW170 01237 12 37 7 30 60 1.27 1256
HW170 01002 10 2 7 30 45 0.45 119
HW170 01003 10 3 7 30 45 0.48 162
HW170 01004 10 4 7 30 60 0.52 207
HW170 01005 10 5 7 30 60 0.58 272
HW170 01007 10 7 7 30 60 0.65 358
HW170 01009 10 9 7 30 60 0.77 459
HW170 01012 10 12 7 30 60 0.91 628
HW170 01019 10 19 7 30 60 1.05 935

Application:
LifeGuard Low Smoke Zero Halogen cable is for use in power, control and lighting circuits in a broad range of commercial and industrial applications. It is highly flame retardant, produces very small amounts of smoke when burned and contains no halogens. LifeGuard™ cable is ideal for applications where a high degree of safety and equipment protection is required.

LifeGuard cable is NEC listed as Type TC-LS and approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays and direct burial in circuits not exceeding 600 volts. It may be installed in temperatures as low as -30°C and used in NEC Class 1, Division 2 hazardous locations. It is NEC approved for continuous operation at 90°C in wet and dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Product Features:
•FM Approved per cable fire propagation Standard 3972, Group 1
•Tray rated
•Sunlight-resistant
•Approved for direct burial
•Tinned conductors provide ease of termination and added protection in caustic environments
•Very low smoke production when burned
•LifeGuard jacket produces zero halogens during fire – less toxic and corrosive
•LifeGuard jacket is environmentally safe – lead, sulfur and halogen free
•Highly chemical resistant
•Very flame retardant
•Burns to an ash – does not exhibit thermoplastic drip
•Excellent compression and impact resistance
•Superior tensile strength and abrasion resistance
•Flexible jacket with low coefficient of friction

Conductors:
Tin coated soft annealed copper per ASTM B-33, Class B stranding per ASTM B-8

Insulation:
Cross-linked polyethylene (XLP) per UL Standard 44 for Type XHHW-2 conductors

Jacket:
•Sunlight-resistant and flame-retardant, Low Smoke Zero Halogen polyolefin per UL Standard 1277
•A ripcord is applied longitudinally under the jacket to facilitate stripping

Flame Tests:
•FM Approved – Class 3972 Specification Test Standard – Cable Fire Propagation Group 1
•UL Standard 1581 70,000 BTU/hr flame test
•IEEE 383 70,000 BTU/hr flame test
•ICEA T-29-520 210,000 BTU/hr flame test
•IEEE 1202/CSA FT4 70,000 BTU/hr flame test
•UL Standard 1685 70,000 BTU/hr Flame Propagation and Smoke Release Test
•Flame Test Listings May Vary By Cable Size

Color Code:
ICEA Method 1, Table E-1 and E-2

Additional Standards:
•NEC Type TC per articles 336, 392, and 501.4 (b) and Class 1 circuits per NEC article 725