POWER CABLE – THHN/THWN, PVC/NYLON

Specification:
HW154
Tray Cable – Power Cable
600 Volt UL Type TC
THHN or THWN Insulation
PVC Jacket
Copper Conductor

Catalog Number Size AWG/
kcmil
No. of Cond. No. of Strands Nylon Jacket Thickness Mils Insulation Thickness Mils Jacket Thickness Mils Ground Wire Size AWG Overall Diameter Inch Net Weight Lbs/Mft
HW154 00803 8 3 7 5 30 60 10 0.58 220
HW154 00804 8 4 7 5 30 60 10 0.61 286
HW154 00603 6 3 7 5 30 60 8 0.69 386
HW154 00604 6 4 7 5 30 60 8 0.76 505
HW154 00403 4 3 7 6 40 60 8 0.89 630
HW154 00404 4 4 7 6 40 80 8 0.97 828
HW154 00203 2 3 7 6 40 80 6 1.03 930
HW154 00204 2 4 7 6 40 80 6 1.13 1213
HW154 00103 1 3 19 7 50 80 6 1.15 1252
HW154 10103 1/0 3 19 7 50 80 6 1.22 1423
HW154 10104 1/0 4 19 7 50 80 6 1.34 1832
HW154 20103 2/0 3 19 7 50 80 6 1.32 1718
HW154 20104 2/0 4 19 7 50 80 6 1.45 2223
HW154 30103 3/0 3 19 7 50 80 4 1.42 2131
HW154 30104 3/0 4 19 7 50 80 4 1.58 2756
HW154 40103 4/0 3 19 7 50 80 4 1.54 2592
HW154 40104 4/0 4 19 7 50 80 4 1.77 3457
HW154 25003 250 3 37 8 60 110 3 1.75 3123
HW154 25004 250 4 37 8 60 110 3 1.94 4046
HW154 35003 350 3 37 8 60 110 3 1.97 4204
HW154 35004 350 4 37 8 60 110 3 2.18 5469
HW154 50003 500 3 37 8 60 110 2 2.26 5792
HW154 50004 500 4 37 8 60 110 1 2.49 7556
HW154 75003 750 3 37 9 60 110 1 2.82 9060

 

Application:
General purpose cable for use in power, control and lighting circuits in a broad range of commercial and industrial applications. Approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 hazardous locations. UL approved for use in continuous operation at 75°C in wet locations, 90°C in dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.

Insulation:
Flame-retardant PVC per UL Standard 83 for Type THHN or THWN wire.

Insulation Jacket:
Clear nylon per UL Standard 83 for Type THHN or THWN wire.

Grounding Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL Standard 1277.

Jacket:
Sunlight-resistant PVC per UL Standard 1277.

Flame Tests:
•IEEE 383 70,000 BTU/hr flame test

Color Code:
ICEA Method 4

Additional Standards:
UL Type TC per Article 336 of the NEC.