POWER CABLE – XHHW-2, VW-1, FR-EP, CPE

Specification:
HW159
Tray Cable – Power Cable
600 Volt UL Type TC, 90°C
FR-EP VW-1 XHHW-2 Insulation
CPE Jacket
Tinned Copper Conductors 

Catalog Number Size AWG/kcmil No. of Conductors No. of Strands Insulation Thickness Mils Jacket Thickness Mils Ground Wire Size AWG Overall Diameter Inch Net Weight Lbs/Mft
HW159 00803 8 3 7 45 60 10 0.66 359
HW159 00804 8 4 7 45 60 10 0.72 439
HW159 00603 6 3 7 45 60 8 0.74 513
HW159 00604 6 4 7 45 60 8 0.81 627
HW159 00403 4 3 7 45 80 8 0.88 721
HW159 00404 4 4 7 45 80 8 0.97 897
HW159 00203 2 3 7 45 80 6 1.01 1063
HW159 00204 2 4 7 45 80 6 1.11 1324
HW159 00103 1 3 19 55 80 6 1.13 1190
HW159 10103 1/0 3 19 55 80 6 1.23 1528
HW159 10104 1/0 4 19 55 80 6 1.34 1934
HW159 20103 2/0 3 19 55 80 6 1.32 1830
HW159 20104 2/0 4 19 55 80 4 1.46 2332
HW159 30103 3/0 3 19 55 80 4 1.43 2500
HW159 30104 3/0 4 19 55 80 4 1.60 2868
HW159 40103 4/0 3 19 55 80 4 1.56 2763
HW159 40104 4/0 4 19 55 110 4 1.79 3630
HW159 25003 250 3 37 65 110 4 1.78 3296
HW159 25004 250 4 37 65 110 3 1.96 4210
HW159 35003 350 3 37 65 110 3 2.00 3643
HW159 35004 350 4 37 65 110 3 2.21 4743
HW159 50003 500 3 37 65 110 2 2.29 6116
HW159 50004 500 4 37 65 110 2 2.54 7881
HW159 75003 750 3 61 80 140 1 2.81 9101

Application:
Superior flame-retardant cable for use in caustic environments in power, control and lighting circuits in a broad range of commercial and industrial applications. Approved for use in wet or dry locations at 90°C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be installed at temperatures as low as -35°C and used in NEC Class I and II, Division 2 hazardous locations. UL approved for use at 90°C for continuous operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductors:
Tin-coated, soft annealed copper per ASTM B-33, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact).

Insulation:
Flame-retardant ethylene-propylene-rubber (FR-EP) per ICEA S-95-658 and UL Standard 44 for Type XHHW-2, VW-1 conductors.

Grounding Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL Standard 1277.

Jacket:
Sunlight-resistant chlorinated polyethylene (CPE) per ICEA S-95-658 and UL Standard 1277.

Flame Tests:
•IEEE 383 70,000 BTU/hr flame test
•IEEE 1202 70,000 BTU/hr CSA FT4 flame test
•UL Standard 1277 70,000 BTU/hr flame test
•ICEA T-29-520 210,000 BTU/hr flame test
•Individual conductors pass the UL VW-1 flame test

Color Code:
ICEA Method 4

Additional Standards:
•UL Type TC per Article 336 of the NEC
•NEMA WC 70