Specification:
HW157
Tray Cable – Power Cable
600 Volt UL Type TC, 90°C
XLP XHHW-2 Insulation
PVC Jacket
Copper Conductors
| Catalog Number | Size AWG/kcmil | No. of Conductors | No. of Strands | Insulation Thickness Mils | Jacket Thickness Mils | Ground Wire Size AWG | Overall Diameter Inch | Net Weight Lbs/Mft |
|---|---|---|---|---|---|---|---|---|
| HW157 00803 | 8 | 3 | 7 | 45 | 60 | 10 | 0.66 | 330 |
| HW157 00804 | 8 | 4 | 7 | 45 | 60 | 10 | 0.72 | 385 |
| HW157 00603 | 6 | 3 | 7 | 45 | 60 | 8 | 0.74 | 460 |
| HW157 00604 | 6 | 4 | 7 | 45 | 60 | 8 | 0.79 | 570 |
| HW157 00403 | 4 | 3 | 7 | 45 | 60 | 8 | 0.86 | 700 |
| HW157 00404 | 4 | 4 | 7 | 45 | 80 | 8 | 0.96 | 830 |
| HW157 00203 | 2 | 3 | 7 | 45 | 80 | 6 | 1.00 | 985 |
| HW157 00204 | 2 | 4 | 7 | 45 | 80 | 6 | 1.10 | 1235 |
| HW157 00103 | 1 | 3 | 19 | 55 | 80 | 6 | 1.13 | 1170 |
| HW157 10103 | 1/0 | 3 | 19 | 55 | 80 | 6 | 1.22 | 1455 |
| HW157 10104 | 1/0 | 4 | 19 | 55 | 80 | 6 | 1.35 | 1840 |
| HW157 20103 | 2/0 | 3 | 19 | 55 | 80 | 6 | 1.32 | 1760 |
| HW157 20104 | 2/0 | 4 | 19 | 55 | 80 | 6 | 1.45 | 2250 |
| HW157 30103 | 3/0 | 3 | 19 | 55 | 80 | 4 | 1.42 | 2120 |
| HW157 30104 | 3/0 | 4 | 19 | 55 | 80 | 4 | 1.58 | 2770 |
| HW157 40103 | 4/0 | 3 | 19 | 55 | 80 | 4 | 1.54 | 2660 |
| HW157 40104 | 4/0 | 4 | 19 | 55 | 110 | 4 | 1.78 | 3500 |
| HW157 25003 | 250 | 3 | 37 | 65 | 110 | 4 | 1.75 | 3300 |
| HW157 25004 | 250 | 4 | 37 | 65 | 110 | 4 | 1.94 | 4160 |
| HW157 35003 | 350 | 3 | 37 | 65 | 110 | 3 | 1.98 | 4360 |
| HW157 35004 | 350 | 4 | 37 | 65 | 110 | 3 | 2.19 | 5670 |
| HW157 50003 | 500 | 3 | 37 | 65 | 110 | 2 | 2.26 | 6190 |
| HW157 50004 | 500 | 4 | 37 | 65 | 140 | 1 | 2.50 | 7890 |
| HW157 75003 | 750 | 3 | 61 | 80 | 140 | 1 | 2.77 | 9500 |
| HW157 75004 | 750 | 4 | 61 | 80 | 140 | 1 | 3.07 | 12100 |
Application:
Superior flame retardant cable for use in power, control and lighting circuits in a broad range of commercial and industrial applications. Approved for use in wet or dry locations at 90C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 hazardous locations. UL approved for use at 90C for continuous operation, 130C for emergency overload conditions, and 250C for short circuit conditions.
Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.
Insulation:
Cross-linked polyethylene (XLP) per ICEA S-95-658 and UL 44 for Type XHHW-2 conductors.
Grounding Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL Standard 1277.
Jacket:
Sunlight-resistant PVC per UL Standard 1277.
Flame Test:
UL and IEEE 383 70,000 BTU/hr flame test.
Color Code:
ICEA Method 4
Additional Standards:
•UL Type TC Tray Cable per Article 336 of the NEC.
•NEMA WC 70