POWER CABLE – XHHW-2, XLP, PVC

Specification:
HW157
Tray Cable – Power Cable
600 Volt UL Type TC, 90°C
XLP XHHW-2 Insulation
PVC Jacket
Copper Conductors

Catalog Number Size AWG/kcmil No. of Conductors No. of Strands Insulation Thickness Mils Jacket Thickness Mils Ground Wire Size AWG Overall Diameter Inch Net Weight Lbs/Mft
HW157 00803 8 3 7 45 60 10 0.66 330
HW157 00804 8 4 7 45 60 10 0.72 385
HW157 00603 6 3 7 45 60 8 0.74 460
HW157 00604 6 4 7 45 60 8 0.79 570
HW157 00403 4 3 7 45 60 8 0.86 700
HW157 00404 4 4 7 45 80 8 0.96 830
HW157 00203 2 3 7 45 80 6 1.00 985
HW157 00204 2 4 7 45 80 6 1.10 1235
HW157 00103 1 3 19 55 80 6 1.13 1170
HW157 10103 1/0 3 19 55 80 6 1.22 1455
HW157 10104 1/0 4 19 55 80 6 1.35 1840
HW157 20103 2/0 3 19 55 80 6 1.32 1760
HW157 20104 2/0 4 19 55 80 6 1.45 2250
HW157 30103 3/0 3 19 55 80 4 1.42 2120
HW157 30104 3/0 4 19 55 80 4 1.58 2770
HW157 40103 4/0 3 19 55 80 4 1.54 2660
HW157 40104 4/0 4 19 55 110 4 1.78 3500
HW157 25003 250 3 37 65 110 4 1.75 3300
HW157 25004 250 4 37 65 110 4 1.94 4160
HW157 35003 350 3 37 65 110 3 1.98 4360
HW157 35004 350 4 37 65 110 3 2.19 5670
HW157 50003 500 3 37 65 110 2 2.26 6190
HW157 50004 500 4 37 65 140 1 2.50 7890
HW157 75003 750 3 61 80 140 1 2.77 9500
HW157 75004 750 4 61 80 140 1 3.07 12100

Application:
Superior flame retardant cable for use in power, control and lighting circuits in a broad range of commercial and industrial applications. Approved for use in wet or dry locations at 90C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 hazardous locations. UL approved for use at 90C for continuous operation, 130C for emergency overload conditions, and 250C for short circuit conditions.

Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.

Insulation:
Cross-linked polyethylene (XLP) per ICEA S-95-658 and UL 44 for Type XHHW-2 conductors.

Grounding Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL Standard 1277.

Jacket:
Sunlight-resistant PVC per UL Standard 1277.

Flame Test:
UL and IEEE 383 70,000 BTU/hr flame test.

Color Code:
ICEA Method 4

Additional Standards:
•UL Type TC Tray Cable per Article 336 of the NEC.
•NEMA WC 70