POWER/CONTROL COMPOSITE – THHN/THWN, PVC/NYLON

Specification:
HW155
Tray Cable – Power & Control Composite Cable
600 Volt UL Type TC
THHN or THWN Insulation
PVC Jacket
Copper Conductor

POWER:

Catalog Number Size AWG No. of Conductors Insulation Thickness Mils Nylon Jacket Thickness Mils Ground Wire Size AWG
HW155 12014 12 3 15 4 12
HW155 10012 10 3 20 4 10
HW155 10014 10 3 20 4 10
HW155 08012 8 3 30 5 10
HW155 08014 8 3 30 5 10
HW155 06012 6 3 30 5 8
HW155 06014 6 3 30 5 8
HW155 04012 4 3 40 6 8
HW155 04014 4 3 40 6 8
HW155 02012 2 3 40 6 6
HW155 02014 2 3 40 6 6

CONTROL:

Catalog Number Size AWG No. of Conductors Insulation Thickness Mils Nylon Jacket Thickness Mils Overall Jacket Thickness Mils Overall Diameter Inch Net Weight Lbs/Mft
HW155 12014 14 4 15 12 45 0.45 190
HW155 10012 12 4 15 10 60 0.58 280
HW155 10014 14 4 15 10 60 0.55 265
HW155 08012 12 4 15 10 60 0.71 392
HW155 08014 14 4 15 10 60 0.67 350
HW155 06012 12 4 15 8 60 0.76 505
HW155 06014 14 4 15 8 60 0.72 458
HW155 04012 12 4 15 8 80 0.94 735
HW155 04014 14 4 15 8 80 0.93 707
HW155 02012 12 4 15 6 80 1.01 1030
HW155 02014 14 4 15 6 80 1.02 980

Application:
General purpose cable for use in power, control and lighting circuits in a broad range of commercial and industrial applications. Approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 hazardous locations. UL approved for use in continuous operation at 75°C in wet locations, 90°C in dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductors:
7-strand soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.

Insulation:
Flame-retardant PVC per UL Standard 83 for Type THHN or THWN wire.

Insulation Jacket:
Clear nylon per UL Standard 83 for Type THHN or THWN wire.

Grounding Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL Standard 1277.

Jacket:
Sunlight-resistant PVC per UL Standard 1277.

Flame Tests:
•IEEE 383 70,000 BTU/hr flame test
•ICEA 210,000 BTU/hr flame test

Color Code:
•Power Sizes: ICEA Method 4
•Control Sizes: ICEA Method 1, Table E-2

Additional Standards:
•UL Type TC per Article 336 of the NEC.
•Approved for Class 1 remote-control and signaling circuits per Article 725 of the NEC.