Specification:
HW152
Tray Cable – Shielded Control Cable
600 Volt UL Type TC
TFN Insulation
PVC Jacket Copper Conductor
| Catalog Number | Size AWG | No. of Conductors | No. of Strands | Nylon Jacket Thickness Mils | Insulation Thickness Mils | Jacket Thickness Mils | Overall Diameter Inch | Net Weight Lbs/Mft |
|---|---|---|---|---|---|---|---|---|
| HW152 01802 | 18 | 2 | 7 | 4 | 15 | 45 | 0.27 | 34 |
| HW152 01803 | 18 | 3 | 7 | 4 | 15 | 45 | 0.28 | 43 |
| HW152 01804 | 18 | 4 | 7 | 4 | 15 | 45 | 0.31 | 52 |
| HW152 01805 | 18 | 5 | 7 | 4 | 15 | 45 | 0.33 | 62 |
| HW152 01806 | 18 | 6 | 7 | 4 | 15 | 45 | 0.36 | 72 |
| HW152 01807 | 18 | 7 | 7 | 4 | 15 | 45 | 0.36 | 79 |
| HW152 01808 | 18 | 8 | 7 | 4 | 15 | 45 | 0.38 | 89 |
| HW152 01812 | 18 | 12 | 7 | 4 | 15 | 45 | 0.46 | 127 |
| HW152 01819 | 18 | 19 | 7 | 4 | 15 | 60 | 0.57 | 202 |
| HW152 01837 | 18 | 37 | 7 | 4 | 15 | 60 | 0.74 | 360 |
| HW152 01602 | 16 | 2 | 7 | 4 | 15 | 45 | 0.29 | 43 |
| HW152 01603 | 16 | 3 | 7 | 4 | 15 | 45 | 0.31 | 55 |
| HW152 01604 | 16 | 4 | 7 | 4 | 15 | 45 | 0.34 | 69 |
| HW152 01605 | 16 | 5 | 7 | 4 | 15 | 45 | 0.36 | 83 |
| HW152 01606 | 16 | 6 | 7 | 4 | 15 | 45 | 0.39 | 96 |
| HW152 01607 | 16 | 7 | 7 | 4 | 15 | 45 | 0.39 | 106 |
| HW152 01608 | 16 | 8 | 7 | 4 | 15 | 45 | 0.43 | 122 |
| HW152 01609 | 16 | 9 | 7 | 4 | 15 | 45 | 0.46 | 138 |
| HW152 01610 | 16 | 10 | 7 | 4 | 15 | 45 | 0.49 | 149 |
| HW152 01612 | 16 | 12 | 7 | 4 | 15 | 45 | 0.51 | 174 |
| HW152 01619 | 16 | 19 | 7 | 4 | 15 | 60 | 0.63 | 275 |
| HW152 01625 | 16 | 25 | 7 | 4 | 15 | 60 | 0.72 | 355 |
| HW152 01637 | 16 | 37 | 7 | 4 | 15 | 80 | 0.82 | 498 |
Application:
General purpose cable for use where shielding from ambient electrical interference is required in power, control and lighting circuits in a broad range of commercial and industrial applications. Approved for continuous operation at 90°C in dry locations, installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 hazardous locations.
Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.
Insulation:
Flame-retardant PVC per UL Standard 62 for Type TFN wire.
Insulation Jacket:
Clear nylon per UL Standard 62 for Type TFN wire.
Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.
Jacket:
Sunlight-resistant PVC per UL Standard 1277.
Flame Tests:
•IEEE 383 70,000 BTU/hr flame test
Color Code:
ICEA Method 1, Table E-2
Additional Standards:
•UL Type TC per Article 336 of the NEC.
•Approved for Class 1 remote-control and signaling circuits per Article 725 of the NEC.