SHIELDED CONTROL CABLE – TFN, PVC/NYLON

Specification:
HW152
Tray Cable – Shielded Control Cable
600 Volt UL Type TC
TFN Insulation
PVC Jacket Copper Conductor

Catalog Number Size AWG No. of Conductors No. of Strands Nylon Jacket Thickness Mils Insulation Thickness Mils Jacket Thickness Mils Overall Diameter Inch Net Weight Lbs/Mft
HW152 01802 18 2 7 4 15 45 0.27 34
HW152 01803 18 3 7 4 15 45 0.28 43
HW152 01804 18 4 7 4 15 45 0.31 52
HW152 01805 18 5 7 4 15 45 0.33 62
HW152 01806 18 6 7 4 15 45 0.36 72
HW152 01807 18 7 7 4 15 45 0.36 79
HW152 01808 18 8 7 4 15 45 0.38 89
HW152 01812 18 12 7 4 15 45 0.46 127
HW152 01819 18 19 7 4 15 60 0.57 202
HW152 01837 18 37 7 4 15 60 0.74 360
HW152 01602 16 2 7 4 15 45 0.29 43
HW152 01603 16 3 7 4 15 45 0.31 55
HW152 01604 16 4 7 4 15 45 0.34 69
HW152 01605 16 5 7 4 15 45 0.36 83
HW152 01606 16 6 7 4 15 45 0.39 96
HW152 01607 16 7 7 4 15 45 0.39 106
HW152 01608 16 8 7 4 15 45 0.43 122
HW152 01609 16 9 7 4 15 45 0.46 138
HW152 01610 16 10 7 4 15 45 0.49 149
HW152 01612 16 12 7 4 15 45 0.51 174
HW152 01619 16 19 7 4 15 60 0.63 275
HW152 01625 16 25 7 4 15 60 0.72 355
HW152 01637 16 37 7 4 15 80 0.82 498

Application:
General purpose cable for use where shielding from ambient electrical interference is required in power, control and lighting circuits in a broad range of commercial and industrial applications. Approved for continuous operation at 90°C in dry locations, installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 hazardous locations.

Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.

Insulation:
Flame-retardant PVC per UL Standard 62 for Type TFN wire.

Insulation Jacket:
Clear nylon per UL Standard 62 for Type TFN wire.

Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Jacket:
Sunlight-resistant PVC per UL Standard 1277.

Flame Tests:
•IEEE 383 70,000 BTU/hr flame test

Color Code:
ICEA Method 1, Table E-2

Additional Standards:
•UL Type TC per Article 336 of the NEC.
•Approved for Class 1 remote-control and signaling circuits per Article 725 of the NEC.

Comments are closed.