SHIELDED CONTROL CABLE – THHN/THWN, PVC/NYLON

Specification:
HW153
Tray Cable – Shielded Control Cable
600 Volt UL Type TC
THHN or THWN Insulation
PVC Jacket
Copper Conductor

Catalog Number Size AWG No. of Conductors No. of Strands Nylon Jacket Thickness Mils Insulation Thickness Mils Jacket Thickness Mils Overall Diameter Inch Net Weight Lbs/Mft
HW153 01402 14 2 7 4 15 45 0.33 62
HW153 01403 14 3 7 4 15 45 0.35 80
HW153 01404 14 4 7 4 15 45 0.38 99
HW153 01405 14 5 7 4 15 45 0.41 118
HW153 01407 14 7 7 4 15 45 0.45 153
HW153 01409 14 9 7 4 15 45 0.52 196
HW153 01412 14 12 7 4 15 60 0.61 267
HW153 01419 14 19 7 4 15 60 0.71 396
HW153 01425 14 25 7 4 15 60 0.83 511
HW153 01437 14 37 7 4 15 60 1.02 768
HW153 01202 12 2 7 4 15 45 0.37 83
HW153 01203 12 3 7 4 15 45 0.39 110
HW153 01204 12 4 7 4 15 45 0.42 138
HW153 01205 12 5 7 4 15 45 0.46 165
HW153 01207 12 7 7 4 15 45 0.50 216
HW153 01209 12 9 7 4 15 60 0.62 297
HW153 01212 12 12 7 4 15 60 0.69 378
HW153 01219 12 19 7 4 15 60 0.80 568
HW153 01237 12 37 7 4 15 60 1.14 1105
HW153 01002 10 2 7 4 20 45 0.43 131
HW153 01003 10 3 7 4 20 45 0.45 169
HW153 01004 10 4 7 4 20 45 0.50 231
HW153 01005 10 5 7 4 20 60 0.58 276
HW153 01012 10 12 7 4 20 60 0.86 647

Application:
General purpose cable for use in power, control and lighting circuits in a broad range of commercial and industrial applications. Approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and II, Division 2 hazardous locations. UL approved for use in continuous operation at 75°C in wet locations, 90°C in dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.

Insulation:
Flame-retardant PVC per UL Standard 83 for Type THHN or THWN wire.

Insulation Jacket:
Clear nylon per UL Standard 83 for Type THHN or THWN wire.

Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Jacket:
Sunlight-resistant PVC per UL Standard 1277.

Flame Tests:
•IEEE 383 70,000 BTU/hr flame test

Color Code:
Control Sizes: ICEA Method 1, Table E-2

Additional Standards:
•UL Type TC per Article 336 of the NEC.
•Approved for Class 1 remote-control and signaling circuits per Article 725 of the NEC.