Specification:
HW173
Tray Cable – Substaion Control Cable
600 Volt UL Type TC-LS, 90°C
Corrugated 5 Mil Copper Tape Shield
XLP XHHW-2 Insulation
Low Smoke Zero Halogen Jacket
FM Approved
| Catalog Number | Size AWG | Number of Conductors | Insulation Thickness | Jacket Thickness | Ground Wire Size AWG | Net Weight Lbs/Mft |
|---|---|---|---|---|---|---|
| HW173 01404 | 14 | 4 | 30 | 45 | 0.48 | 144 |
| HW173 01407 | 14 | 7 | 30 | 45 | 0.60 | 231 |
| HW173 01412 | 14 | 12 | 30 | 60 | 0.75 | 348 |
| HW173 01419 | 14 | 19 | 30 | 80 | 0.90 | 534 |
| HW173 01204 | 12 | 4 | 30 | 45 | 0.52 | 182 |
| HW173 01207 | 12 | 7 | 30 | 45 | 0.65 | 296 |
| HW173 01212 | 12 | 12 | 30 | 60 | 0.82 | 463 |
| HW173 01219 | 12 | 19 | 30 | 80 | 0.99 | 718 |
| HW173 01004 | 10 | 4 | 30 | 45 | 0.62 | 265 |
| HW173 01007 | 10 | 7 | 30 | 60 | 0.72 | 408 |
| HW173 01012 | 10 | 12 | 30 | 80 | 0.96 | 695 |
| HW173 01019 | 10 | 19 | 30 | 80 | 1.12 | 1015 |
Application:
LifeGuard Low Smoke Zero Halogen cable is for use in power, control and lighting circuits in a broad range of utility substation applications where shielding from ambient electrical interference is required. It is highly flame retardant, produces very small amounts of smoke when burned and contains no halogens. LifeGuard cable is ideal for applications where a high degree of safety and equipment protection is required.
LifeGuard cable is NEC listed as Type TC-LS and approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays and direct burial in circuits not exceeding 600 volts. It may be installed in temperatures as low as -30°C and used in NEC Class I and II, Division 2 hazardous locations. It is NEC approved for continuous operation at 90°C in wet and dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions.
Product Features:
•FM Approved per cable fire propagation Standard 3972, Group 1
•Tray rated
•Sunlight-resistant
•Approved for direct burial
•Tinned conductors provide ease of termination and added protection in caustic environments
•Superior electrostatic interference protection from copper tape shield
•Superior conductor protection from copper tape shield
•Very low smoke production when burned
•LifeGuard jacket produces zero halogens during fire – less toxic and corrosive
•LifeGuard jacket is environmentally safe – lead, sulfur and halogen free
•Highly chemical resistant
•Very flame retardant
•Burns to an ash – does not exhibit thermoplastic drip
•Excellent compression and impact resistance
•Superior tensile strength and abrasion resistance
•Flexible jacket with low coefficient of friction
Conductors:
Tin coated soft annealed copper per ASTM B-33, Class B stranding per ASTM B-8
Insulation:
Cross-linked polyethylene (XLP) per UL Standard 44 for Type XHHW-2 conductors
Overall Shield:
Longitudinally applied 5 mil corrugated copper tape shield
Jacket:
•Sunlight-resistant and flame-retardant, Low Smoke Zero Halogen polyolefin per UL Standard 1277
•A ripcord is applied longitudinally under the jacket to facilitate stripping
Flame Test:
•FM Approved – Class 3972 Specification Test Standard – Cable Fire Propagation Group 1
•UL Standard 1581 70,000 BTU/hr flame test
•IEEE 383 70,000 BTU/hr flame test
•ICEA T-29-520 210,000 BTU/hr flame test
•IEEE 1202/CSA FT4 70,000 BTU/hr flame test
•UL Standard 1685 70,000 BTU/hr Flame Propagation and Smoke Release Test
•Flame Test Listings May Vary By Cable Size
Color Code:
ICEA Method 1, Table E-1
Additional Standards:
•NEC Type TC per articles 336, 392, and 501.4 (b) and Class 1 circuits per NEC article 725.