PORTABLE POWER – 2000V POWER CABLE – G-GC

Specification:
HW259
Portable Power Cable – Type G-GC
2000 Volt, -40°C to +90°C
Three Conductor
EPR Insulation, CPE Jacket
Flexible Copper Conductors

Catalog Number Size AWG/kcmil No. of Strands Insulation Thickness Mils Jacket Thickness Mils Grounding Conductor Size AWG Ground Check Conductor Size Overall Diameter Inch Net Weight Lbs/Mft
HW259 00803 8 133 60 143 10 10 0.97 675
HW259 00603 6 133 60 152 10 10 1.05 825
HW259 00403 4 259 60 172 8 10 1.19 1125
HW259 00203 2 259 60 180 7 10 1.34 1525
HW259 00103 1 259 80 193 6 8 1.51 1795
HW259 10103 1/0 259 80 203 5 8 1.65 2390
HW259 20103 2/0 259 80 198 4 8 1.75 2790
HW259 30103 3/0 259 80 185 3 8 1.89 3426
HW259 40103 4/0 259 80 207 2 8 2.04 4030
HW259 25003 250 427 95 267 2 8 2.38 5445
HW259 35003 350 427 95 283 1/0 8 2.73 7273
HW259 50003 500 427 95 295 2/0 8 3.02 9439

 
Application:
Portable power cable designed for heavy duty temporary or permanent use where maximum resistance to flex fatigue is required. Used in extremely demanding applications including mobile mining equipment, cutters, loaders, conveyors, drills and pumps. For three-phase alternating current circuits, not to exceed 2,000 volts, where grounding conductors and ground check conductors are required.

Conductors:
Soft bare annealed copper per ASTM B-3, flexible rope lay strand.

Insulation:
Ethylene propylene diene monomer (EPDM) rubber.

Grounding Conductors:
Two insulated ground and one insulated ground check, soft bare annealed copper conductors per ASTM B-3, flexible strand sized in accordance with applicable ICEA standards.

Assembly:
Multiple conductor constructions cabled with fillers for roundness, with an open reinforcement over the assembly for mechanical protection.

Jacket:
Chlorinated polyethylene (CPE) rubber.

Flame Tests:
•MSHA flame test

Color Code:
Black, White, Red

Additional Standards:
•ICEA S-75-381
•Pennsylvania Bureau of Mines – MSHA approved

Comments are closed.