PORTABLE POWER – 2000V POWER CABLE – SINGLE CONDUCTOR – W

Specification:
HW256
Portable Power Cable – Type W
2000 Volt UL, -40°C to +90°C
EPR Insulation, CPE Jacket
Single, Flexible Copper Conductor

Catalog Number Size AWG/kcmil No. of Strands Insulation Thickness Mils Jacket Thickness Mils Overall Diameter Inch Net Weight Lbs/Mft
HW256 00801 8 133 60 75 0.44 155
HW256 00601 6 259 60 95 0.53 267
HW256 00401 4 259 60 95 0.60 369
HW256 00201 2 259 60 95 0.66 458
HW256 10101 1/0 259 80 95 0.79 658
HW256 20101 2/0 259 80 95 0.81 730
HW256 40101 4/0 259 80 95 0.95 1049
HW256 25001 250 627 95 95 1.08 1425
HW256 35001 350 855 95 95 1.20 1971
HW256 50001 500 1235 95 95 1.34 2651

Application:
Portable power cable designed for heavy duty temporary or permanent use where maximum resistance to flex fatigue is required. Used in extremely demanding applications including trailing cable on mobile mining equipment, diesel electric locomotives, lifting magnets, cranes, cutters, loaders, conveyors, drills and pumps where grounded circuits are not required. For use in circuits not to exceed 2000 volts.

Conductor:
Soft bare annealed copper, rope stranded per ICEA S-75-381 part 2 and UL requirements.

Insulation:
Ethylene propylene rubber (EPR) per ICEA S-75-381.

Jacket:
Chlorinated polyethylene (CPE) rubber per ICEA S-75-381.

Flame Tests:
MSHA flame test

Additional Standards:
Pennsylvania Bureau of Mines – MSHA approved

Note:
Sizes 1/0 AWG and larger are non-UL constructions made in accordance with applicable industry standards.