INSTRUMENTATION – 300 VOLT TYPE PLTC – MULTIPLE PAIRS I/S & O/S – PVC

Specification:
HW103
Instrumentation Cable
300 Volt UL Type PLTC & ITC, 105°C
Multiple Pairs
Individual and Overall Shield
PVC Insulation
PVC Jacket
Copper Conductors

Catalog Number Size AWG Pair/Triad Isulation Thickness Mils Jacket Thickness Mils Overall Diameter In. Net Weight Lbs/Mft
HW103 02002 20 2 15 40 0.36 61
HW103 02004 20 4 15 50 0.46 110
HW103 02008 20 8 15 50 0.58 182
HW103 02012 20 12 15 60 0.71 267
HW103 02016 20 16 15 60 0.81 315
HW103 02024 20 24 15 70 0.97 492
HW103 02036 20 36 15 70 1.11 685
HW103 02050 20 50 15 70 1.33 768
HW103 01802 18 2 15 40 0.40 76
HW103 01804 18 4 15 50 0.50 134
HW103 01808 18 8 15 50 0.63 226
HW103 01812 18 12 15 60 0.78 332
HW103 01816 18 16 15 60 0.89 374
HW103 01824 18 24 15 70 1.08 619
HW103 01836 18 36 15 70 1.23 869
HW103 01850 18 50 15 80 1.49 1047
HW103 01602 16 2 15 50 0.47 107
HW103 01604 16 4 15 50 0.55 178
HW103 01608 16 8 15 60 0.73 323
HW103 01612 16 12 15 60 0.87 456
HW103 01616 16 16 15 70 1.02 529
HW103 01624 16 24 15 70 1.21 860
HW103 01636 16 36 15 80 1.40 1250
HW103 01650 16 50 15 80 1.68 1453

Application:
For use in instrumentation and process control applications where protection from electrostatic interference is required. UL listed as Type PLTC and ITC and approved for installation indoors or outdoors, aerially, in conduits, ducts and cable trays in circuits not exceeding 300 volts. May be used in NEC Class 1, Division 2 hazardous locations.

Conductors:
7-strand soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.

Insulation:
Flame-retardant PVC.

Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Jacket:
Sunlight-resistant PVC. A ripcord is applied longitudinally under the jacket to facilitate stripping.

Flame Tests:
•UL 1581 70,000 BTU/hr flame test
•CSA FT4 rated

Color Code:
•ICEA Method 9: black and white pairs with printed number
•Available upon request: black and red pairs with printed number

Additional Standards:
•UL Standard 13
•UL Standard 2250
•NEC Type ITC per Articles 501, 502, 503, and 504
•Approved for Class 2 and Class 3 circuits per Article 725 of the NEC

Comments are closed.