Specification:
HW106
Instrumentation Cable
600 Volt UL Type TC, 90°C
Multiple Pairs
Individual and Overall Shield
TFN Insulation
PVC Jacket
Copper Conductors
| Catalog Number | Size AWG | Pair/Triad | Isulation Thickness Mils | Jacket Thickness Mils | Overall Diameter In. | Net Weight Lbs/Mft |
|---|---|---|---|---|---|---|
| HW106 01802 | 18 | 2 | 15 | 4 | 45 | 0.44 |
| HW106 01804 | 18 | 4 | 15 | 4 | 45 | 0.52 |
| HW106 01808 | 18 | 8 | 15 | 4 | 60 | 0.71 |
| HW106 01812 | 18 | 12 | 15 | 4 | 60 | 0.85 |
| HW106 01816 | 18 | 16 | 15 | 4 | 80 | 1.05 |
| HW106 01824 | 18 | 24 | 15 | 4 | 80 | 1.20 |
| HW106 01836 | 18 | 36 | 15 | 4 | 80 | 1.37 |
| HW106 01850 | 18 | 50 | 15 | 4 | 80 | 1.71 |
| HW106 01602 | 16 | 2 | 15 | 4 | 45 | 0.48 |
| HW106 01603 | 16 | 3 | 15 | 4 | 45 | 0.56 |
| HW106 01604 | 16 | 4 | 15 | 4 | 60 | 0.63 |
| HW106 01606 | 16 | 6 | 15 | 4 | 60 | 0.77 |
| HW106 01608 | 16 | 8 | 15 | 4 | 60 | 0.81 |
| HW106 01612 | 16 | 12 | 15 | 4 | 80 | 1.11 |
| HW106 01616 | 16 | 16 | 15 | 4 | 80 | 1.56 |
| HW106 01624 | 16 | 24 | 15 | 4 | 80 | 1.39 |
| HW106 01636 | 16 | 36 | 15 | 4 | 80 | 1.59 |
| HW106 01650 | 16 | 50 | 15 | 4 | 110 | 1.96 |
Application:
For use in instrumentation and process control applications where protection from electrostatic interference is required. UL listed as Type PLTC and ITC and approved for installation indoors or outdoors, aerially, in conduits, ducts and cable trays in circuits not exceeding 600 volts. May be used in NEC Class 1, Division 2 hazardous locations.
Conductors:
7-strand soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.
Insulation:
Flame-retardant PVC per UL Standard 62 for Type TFN wire.
Insulation Jacket:
Clear nylon per UL Standard 62 for Type TFN wire.
Individual Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.
Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire. Jacket: Sunlight-resistant PVC per UL Standard 1277. A ripcord is applied longitudinally under the jacket to facilitate stripping.
Flame Tests:
UL 1581 70,000 BTU/hr flame test
Color Code:
•ICEA Method 9: black and white pairs with printed number
•Available upon request: black and red pairs with printed number
Additional Standards:
•NEC Type TC for Class I Division 2 areas per Articles 336, 392 and 501, and for Class 1 circuits per NEC Article 725
•NEC Type NPFL for Non Power Limited Fire Protective Signaling circuits per NEC Article 760