INSTRUMENTATION – 600 VOLT TYPE TC – MULTIPLE PAIRS I/S & O/S – THHN THWN PVC/NYLON

Specification:
HW107
Instrumentation Cable
600 Volt UL Type TC, 90°C
Multiple Pairs
Individual and Overall Shield
THHN or THWN Insulation
PVC Jacket
Copper Conductors

Catalog Number Size AWG No. of Pairs PVC Isulation Thickness Mils Nylon Jacket Thickness Mils Overall Jacket Thickness Mils Overall Diameter In. Net Weight Lbs/Mft
HW107 01402 14 2 15 4 45 0.57 156
HW107 01404 14 4 15 4 60 0.73 285
HW107 01408 14 8 15 4 60 0.93 520
HW107 01412 14 12 15 4 80 1.16 788
HW107 01424 14 24 15 4 80 1.58 1445

Application:
For use in instrumentation and process control applications where protection from electrostatic interference is required. UL listed as Type PLTC and ITC and approved for installation indoors or outdoors, aerially, in conduits, ducts and cable trays in circuits not exceeding 600 volts. May be used in NEC Class 1, Division 2 hazardous locations. UL approved for NEC continuous operation at 75?C in wet locations, 90?C in dry locations, 130?C for emergency overland conditions, and 250?C for short circuit locations.

Conductors:
7-strand soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.

Insulation:
Flame-retardant PVC per UL Standard 83 for Type THHN or THWN-2 wire.

Insulation Jacket:
Clear nylon per UL Standard 83 for Type THHN or THWN wire.

Individual Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Jacket:
Sunlight-resistant PVC per UL Standard 1277. A ripcord is applied longitudinally under the jacket to facilitate stripping.

Flame Tests:
UL 1581 70,000 BTU/hr flame test

Color Code:
•ICEA Method 9: black and white pairs with printed number
•Available upon request: black and red pairs with printed number

Additional Standards:
•NEC Type TC for Class I Division 2 areas per Articles 336, 392 and 501, and for Class 1 circuits per NEC Article 725
•NEC Type NPFL for Non Power Limited Fire Protective Signaling circuits per NEC Article 760

Comments are closed.