INSTRUMENTATION – 600 VOLT TYPE TC – MULTIPLE PAIRS O/S – TFN PVC/NYLON

Specification:
HW105
INSTRUMENTATION CABLE
600 Volt UL Type TC, 90°C
Multiple Pairs
Overall Shield
TFN Insulation
PVC Jacket
Copper Conductors
 

Catalog Number Size AWG Pair/Triad Isulation Thickness Mils Jacket Thickness Mils Overall Diameter In. Net Weight Lbs/Mft
HW105 01802 18 2 15 4 45 0.41
HW105 01804 18 4 15 4 45 0.49
HW105 01808 18 8 15 4 60 0.65
HW105 01812 18 12 15 4 60 0.76
HW105 01816 18 16 15 4 80 0.89
HW105 01824 18 24 15 4 80 1.03
HW105 01836 18 36 15 4 80 1.18
HW105 01850 18 50 15 4 80 1.44
HW105 01602 16 2 15 4 45 0.45
HW105 01603 16 3 15 4 45 0.52
HW105 01604 16 4 15 4 45 0.57
HW105 01608 16 8 15 4 60 0.75
HW105 01612 16 12 15 4 60 0.88
HW105 01616 16 16 15 4 80 1.03
HW105 01624 16 24 15 4 80 1.21
HW105 01636 16 36 15 4 80 1.40
HW105 01650 16 50 15 4 80 1.61

 
Application:
For use in instrumentation and process control applications where protection from electrostatic interference is required. UL listed as Type PLTC and ITC and approved for installation indoors or outdoors, aerially, in conduits, ducts and cable trays in circuits not exceeding 600 volts. May be used in NEC Class 1, Division 2 hazardous locations.

Conductors:
7-strand soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8.

Insulation:
Flame-retardant PVC.

Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Jacket:
Sunlight-resistant PVC. A ripcord is applied longitudinally under the jacket to facilitate stripping.

Flame Tests:
•UL 1581 70,000 BTU/hr flame test
•CSA FT4 rated

Color Code:
•ICEA Method 9: black, white and red triads with printed number
•Available upon request: black, red and blue triads with printed number

Additional Standards:
•UL Standard 13
•UL Standard 2250
•NEC Type ITC per Articles 501, 502, 503, and 504
•Approved for Class 2 and Class 3 circuits per Article 725 of the NEC