INSTRUMENTATION – 600 VOLT TYPE TC – MULTIPLE TRIADS I/S & O/S – TFN PVC/NYLON

Specification:
HW108
Instrumentation Cable
600 Volt UL Type TC, 90°C
Multiple Triads
Individual and Overall Shield
TFN Insulation
PVC Jacket
Copper Conductors 

Catalog Number Size AWG No. of Triads PVC Isulation Thickness Mils Nylon Jacket Thickness Mils Overall Jacket Thickness Mils Overall Diameter In. Net Weight Lbs/Mft
HW108 01804 18 4 15 4 60 0.61 207
HW108 01808 18 8 15 4 60 0.78 355
HW108 01812 18 12 15 4 80 0.98 538
HW108 01824 18 24 15 4 80 1.33 971
HW108 01604 16 4 15 4 60 0.67 233
HW108 01608 16 8 15 4 60 0.90 401
HW108 01612 16 12 15 4 80 1.08 607
HW108 01616 16 16 15 4 80 1.27 838
HW108 01624 16 24 15 4 80 1.48 1100

 
Application:
For use in instrumentation and process control applications where protection from electrostatic interference is required. UL listed as Type PLTC and ITC and approved for installation indoors or outdoors, aerially, in conduits, ducts and cable trays in circuits not exceeding 600 volts. May be used in NEC Class 1, Division 2 hazardous locations. UL approved for NEC continuous operation at 75?C in wet locations, 90?C in dry locations, 130?C for emergency overland conditions, and 250?C for short circuit locations.

Conductors:
7-strand soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8. Insulation: Flame-retardant PVC per UL Standard 62 for Type TFN wire.

Insulation Jacket:
Clear nylon per UL Standard 62 for Type TFN wire.

Individual Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Jacket:
Sunlight-resistant PVC per UL Standard 1277. A ripcord is applied longitudinally under the jacket to facilitate stripping.

Flame Tests:
UL 1581 70,000 BTU/hr flame test

Color Code:
•ICEA Method 1: black, white and red triads with printed number
•Available upon request: black, red and blue triads with printed number

Additional Standards:
•NEC Type TC for Class I Division 2 areas per Articles 336, 392 and 501, and for Class 1 circuits per NEC Article 725
•NEC Type NPFL for Non Power Limited Fire Protective Signaling circuits per NEC Article 760

Comments are closed.