Specification:
HW114
Thermocouple Extension Cable – EX JX KX TX
300 Volt UL Type PLTC & ITC, 200°C
Single Pair
Overall Shield
FEP Teflon Insulation
FEP Teflon Jacket
Solid Alloy Conductor
| Catalog Number | Size AWG | No. of Pairs | Isulation Thickness Mils | Jacket Thickness Mils | ANSI Type | Overall Diameter In. | Net Weight Lbs/Mft |
|---|---|---|---|---|---|---|---|
| HW114 1602E | 16 | 1 | 10 | 12 | E X | 0.17 | 32 |
| HW114 1602J | 16 | 1 | 10 | 12 | J X | 0.17 | 31 |
| HW114 1602K | 16 | 1 | 10 | 12 | K X | 0.17 | 31 |
| HW114 1602T | 16 | 1 | 10 | 12 | T X | 0.17 | 32 |
Application:
For use in high temperature thermocouple extension applications in caustic environments where protection from electrostatic interference is required. UL listed as Type PLTC and approved for installation indoors or outdoors, aerially, in conduits, ducts and cable trays in circuits not exceeding 300 volts. May be used in NEC Class 1, Division 2 hazardous locations.
Conductors:
Annealed, solid thermocouple extension grade alloys calibrated to standard limits of error per ANSI-MC96.1.
Insulation:
FEP Teflon color coded per ANSI-MC96.1.
Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.
Jacket:
FEP Teflon color coded per ANSI-MC96.1. A ripcord is applied longitudinally under the jacket to facilitate stripping.
Flame Tests:
•UL Standard 13 70,000 BTU/hr flame test
•UL 910 Steiner tunnel flame test
•Meets CSA FT4/FT6 flame test
Additional Standards:
•NEC Type ITC per Articles 501, 502, 503, and 504
•NEC Type CL3P/PLTC