THERMOCOUPLE EXTENTION – EX, JX, KX, TX – 300 VOLT TYPE PLTC – SINGLE/MULTIPLE PAIRS O/S – PVC

Specification:
HW111
Thermocouple Extension Cable
300 Volt UL Type PLTC & ITC, 105°C
Single and Multiple Pairs
Overall Shield
PVC Insulation
PVC Jacket
Solid Alloy Conductor

Catalog Number Size AWG No. of Pairs Isulation Thickness Mils Jacket Thickness Mils ANSI Type Overall Diameter In. Net Weight Lbs/Mft
HW111 2004E 20 4 15 40 E X 0.40 78
HW111 2004J 20 4 15 40 J X 0.40 78
HW111 2004K 20 4 15 40 K X 0.40 78
HW111 2004T 20 4 15 40 T X 0.40 78
HW111 2008E 20 8 15 50 E X 0.52 143
HW111 2008J 20 8 15 50 J X 0.52 143
HW111 2008K 20 8 15 50 K X 0.52 143
HW111 2008T 20 8 15 50 T X 0.52 143
HW111 2012E 20 12 15 50 E X 0.61 195
HW111 2012J 20 12 15 50 J X 0.61 195
HW111 2012K 20 12 15 50 K X 0.61 195
HW111 2012T 20 12 15 50 T X 0.61 195
HW111 2016E 20 16 15 50 E X 0.66 257
HW111 2016J 20 16 15 50 J X 0.66 257
HW111 2016K 20 16 15 50 K X 0.66 257
HW111 2016T 20 16 15 50 T X 0.66 257
HW111 2024E 20 24 15 50 E X 0.81 356
HW111 2024J 20 24 15 60 J X 0.81 356
HW111 2024K 20 24 15 60 K X 0.81 356
HW111 2024T 20 24 15 60 T X 0.81 356
HW111 2036J 20 36 15 70 J X 0.95 513
HW111 2036K 20 36 15 70 K X 0.95 513
HW111 2036T 20 36 15 70 T X 0.95 513
HW111 1601E 16 1 15 35 E X 0.28 46
HW111 1601J 16 1 15 35 J X 0.28 46
HW111 1601K 16 1 15 35 K X 0.28 46
HW111 1601T 16 1 15 35 T X 0.28 46

Application:
For use in thermocouple extension applications where protection from electrostatic interference is required. UL listed as Type PLTC and approved for installation indoors or outdoors, aerially, in conduits, ducts and cable trays in circuits not exceeding 300 volts. May be used in NEC Class 1, Division 2 hazardous locations.

Conductors:
Annealed, solid thermocouple extension-grade alloys calibrated to standard limits of error per ANSI-MC96.1.

Insulation:
Flame-retardant PVC per UL Standard 13, color coded per ANSI-MC96.1.

Communication Wire:
Multipair constructions contain a 7-strand bare copper orange PVC-insulated communication wire.

Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Jacket:
Sunlight-resistant PVC color coded per ANSI-MC96.1. A ripcord is applied longitudinally under the jacket to facilitate stripping.

Flame Tests:
UL 1581 70,000 BTU/hr flame test

Additional Standards:
NEC Type ITC approved for use in hazardous locations per Articles 501, 502, 503 and 504