Specification:
HW210
Power Cable – Unishield
15KV UL Type MV-105, 105°C
Single Conductor, Shielded
EPR Insulation, CPE Jacket
133% Insulation Level
Copper Conductor
| Catalog Number | Size AWG/ kcmil |
No. of Strands | Insul. Thickness Mils | Jacket Thickness Mils | Insul. Diameter Inch | Drain Wire Size AWG | Cond. Diameter Inch | Overall Diameter Inch | Net Weight Lbs/Mft |
|---|---|---|---|---|---|---|---|---|---|
| HW210 00201 | 2 | 7 | 220 | 80 | 0.76 | 19 | 0.27 | 0.94 | 574 |
| HW210 10101 | 1/0 | 19 | 220 | 80 | 0.83 | 18 | 0.34 | 1.02 | 753 |
| HW210 20101 | 2/0 | 19 | 220 | 80 | 0.87 | 18 | 0.38 | 1.07 | 867 |
| HW210 40101 | 4/0 | 19 | 220 | 80 | 0.97 | 18 | 0.48 | 1.17 | 1171 |
| HW210 25001 | 250 | 37 | 220 | 85 | 1.03 | 17 | 0.53 | 1.24 | 1349 |
| HW210 35001 | 350 | 37 | 220 | 85 | 1.12 | 17 | 0.62 | 1.33 | 1720 |
| HW210 50001 | 500 | 37 | 220 | 85 | 1.25 | 17 | 0.72 | 1.46 | 2267 |
| HW210 75001 | 750 | 61 | 220 | 100 | 1.43 | 16 | 0.91 | 1.67 | 3216 |
| HW210 10001 | 1000 | 61 | 220 | 115 | 1.59 | 15 | 1.06 | 1.86 | 4164 |
Application:
For use in power circuits up to 15KV when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for critical applications in harsh and caustic environments in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.
Conductor:
Compact soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-496, with a semi-conducting conductor shield.
Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682.
Shield:
Six (6) corrugated copper shield wires longitudinally embedded in an exterior semi-conducting CPE jacket per ICEA S-97-682.
Jacket:
Sunlight-resistant CPE per ICEA S-97-682 and UL Standard 1072.
Flame Tests:
•IEEE 383 70,000 BTU/hr flame test – CT-listed sizes 1/0AWG and larger
•IEEE1202 70,000 BTU/hr, CSA FT4 flame test
•ICEA T-29-520 210,000 BTU/hr flame test
Additional Standards:
•ICEA S-93-639
•NEMA WC74
•AEIC CS8
Note:
CT rated on sizes 1/0 AWG and larger.

Pingback: Wire unishield | Bewaretheclett