2.4kV 3-CONDUCTOR NON SHIELDED 133% – EPR – PVC

Specification:
HW212
Power Cable
2.4KV UL Type MV-105, 105°C
Three Conductor, Non-Shielded
EPR Insulation, PVC Jacket
2.4KV 133% Insualtion Level
Copper Conductor 

Catalog Number Size AWG/kcmil No. of Strands Insulation Thickness Mils Jacket Thickness Mils Insulation Diameter Inch Explosion Proof Connector UN Copper Grounding Condutor AWG Overall Diameter Inch Net Weight Lbs/Mft
HW212 00603 6 7 115 80 0.45 424UN05 6 1.16 795
HW212 00403 4 7 115 80 0.5 424UN06 6 1.26 1010
HW212 00203 2 7 115 80 0.56 424UN06 6 1.39 1305
HW212 00103 1 19 115 80 0.6 424UN06 4 1.48 1600
HW212 10103 1/0 19 115 80 0.64 424UN06 4 1.56 1890
HW212 20103 2/0 19 115 80 0.68 424UN07 4 1.66 2150
HW212 30103 3/0 19 115 110 0.73 424UN07 3 1.83 2650
HW212 40103 4/0 19 115 110 0.79 424UN07 3 1.95 3220
HW212 25003 250 37 115 110 0.84 424UN07 3 2.07 3830
HW212 35003 350 37 115 110 0.95 424UN08 2 2.3 4965
HW212 50003 500 37 115 110 1.08 424UN09 1 2.58 6610
HW212 75003 750 61 115 140 1.27 - – - 1 3.05 9490

 
Application:
For use in primary power and distribution circuits up to 2.4kv when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. National Electric Code approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.

Insulation:
Ethylene propylene rubber (EPR) per ICEA standards.

Grounding Conductor:
Compressed soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance to UL Standard 1072.

Jacket:
Sunlight-resistant PVC per ICEA Standards and UL Standard 1072.

Flame Tests:
UL and IEEE 383 70,000 BTU/hr flame test – CT-listed sizes 1/0AWG and larger.

Color Code:
ICEA Method 4

Additional Standards:
•ICEA S-96-659
•NEMA WC71

Connectors:
Explosion Proof, Class I, Division 2: 424UN series – aluminum exterior components, nickel-plated brass interior components.

Note:
CT rating must be requested. CT ratings are available on all sizes.