2.4kV NON-SHIELDED 133% – EPR – HYPALON

Specification:
HW201
Power Cable
2.4KV UL Type MV-90, 90°C
Single Conductor, Non-Shielded
EPR Insulation, Hypalon Jacket – Heavy Wall
2.4KV 133% Insulation Level
Copper Conductor

Catalog Number Size AWG/kcmil No. of Strands Insulation Thickness Mils Jacket Thickness Mils Overall Diameter Inch Net Weight Lbs/Mft
HW201 00801 8 7 125 80 0.57 195
HW201 00601 6 7 125 80 0.65 260
HW201 00401 4 7 125 80 0.70 330
HW201 00201 2 7 125 80 0.76 405
HW201 00101 1 19 125 80 0.80 505
HW201 10101 1/0 19 125 80 0.84 590
HW201 20101 2/0 19 125 80 0.88 700
HW201 30101 3/0 19 125 95 0.96 860
HW201 40101 4/0 19 125 95 1.02 1020
HW201 25001 250 37 140 110 1.14 1210
HW201 35001 350 37 140 110 1.24 1525
HW201 50001 500 37 140 110 1.37 2130
HW201 75001 750 61 155 125 1.62 3090
HW201 10001 1000 61 155 125 1.76 3960

Application:
For use in caustic environments in power circuits up to 2.4kv when installed in open air, conduit, duct, cable tray when CT rated, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. National Electric Code approved for use at 90°C for continuous operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.

Insulation:
Ethylene propylene rubber (EPR) per ICEA standards.

Jacket:
Chlorosulfonated polyethylene (CSPE/Hypalon?) per ICEA standards.

Flame Tests:
UL and IEEE 383 70,000 BTU/hr flame test ? for CT-listed sizes 1/0 AWG and larger.

Additional Standards:
•ICEA S-96-659
•UL Standard 1072
•NEMA WC71

Note:

•CT rating must be requested. CT ratings are available on sizes 1/0 AWG and larger.
•PVC jacket available upon request.