Specification:
HW211
Power Cable
25KV/35KV UL Type MV-105, 105°C
Single Conductor, Shielded
EPR Insulation, PVC Jacket
25KV 133%, 35KV 100% Insulation Level
Copper Conductor
| Catalog Number | Size AWG/kcmil | No. of Strands | Insulation Thickness Mils | Jacket Thickness Mils | Insulation Diameter Inch | Overall Diameter Inch | Net Weight Lbs/Mft |
|---|---|---|---|---|---|---|---|
| HW211 10101 | 1/0 | 19 | 345 | 80 | 1.11 | 1.39 | 1160 |
| HW211 20101 | 2/0 | 19 | 345 | 80 | 1.15 | 1.44 | 1290 |
| HW211 30101 | 3/0 | 19 | 345 | 80 | 1.20 | 1.49 | 1445 |
| HW211 40101 | 4/0 | 19 | 345 | 80 | 1.26 | 1.53 | 1635 |
| HW211 25001 | 250 | 37 | 345 | 80 | 1.34 | 1.59 | 1805 |
| HW211 35001 | 350 | 37 | 345 | 80 | 1.43 | 1.69 | 2205 |
| HW211 50001 | 500 | 37 | 345 | 110 | 1.56 | 1.90 | 2920 |
| HW211 75001 | 750 | 61 | 345 | 110 | 1.75 | 2.09 | 3895 |
| HW211 10001 | 1000 | 61 | 345 | 110 | 1.90 | 2.24 | 4840 |
Application:
For use in power circuits up to 35KV when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.
Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.
Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682.
Shield:
Uncoated copper tape with a minimum 12.5% overlap per ICEA S-97-682.
Jacket:
Sunlight-resistant PVC per ICEA S-97-682 and UL Standard 1072.
Flame Tests:
IEEE 383 70,000 BTU/hr flame test – CT-rated material.
Additional Standards:
•ICEA S-93-639
•NEMA WC74
•AEIC CS8
•Federal Specification J-C-30B
Note:
CT ratings are available on sizes 1/0AWG and larger.