5kV SHIELDED 100% OR 133% – XLP – PVC

Specification:
HW202
Power Cable
5KV UL Type MV-90, 90°C
Single Conductor, Shielded
XLP Insulation, PVC Jacket
100% or 133% Insulation Level
Copper Conductor

Catalog Number Size AWG/kcmil No. of Strands Insulation Thickness Mils Jacket Thickness Mils Insulation Diameter Inch Overall Diameter Inch Net Weight Lbs/Mft
HW202 00801 8 7 90 60 0.34 0.58 165
HW202 00601 6 7 90 60 0.38 0.6 205
HW202 00401 4 7 90 60 0.45 0.71 290
HW202 00201 2 7 90 60 0.51 0.77 385
HW202 00101 1 19 90 60 0.55 0.81 440
HW202 10101 1/0 19 90 80 0.59 0.89 565
HW202 20101 2/0 19 90 80 0.63 0.94 665
HW202 30101 3/0 19 90 80 0.68 0.99 790
HW202 40101 4/0 19 90 80 0.74 1.04 950
HW202 25001 250 37 90 80 0.80 1.10 1095
HW202 35001 350 37 90 80 0.90 1.21 1445
HW202 50001 500 37 90 80 1.03 1.35 1960
HW202 75001 750 61 90 80 1.22 1.54 2825
HW202 10001 1000 61 90 80 1.37 1.69 3645

 

Application:
For use in power circuits up to 5KV when installed in open air, conduit, duct, or direct buried in earth, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. UL approved for use at 90°C for continuous operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.

Insulation:
Cross-linked polyethylene (XLP) per ICEA S-97-682 with a semi-conducting insulation shield.

Shield:
Shielding wires meet ICEA standards.

Jacket:
Sunlight-resistant PVC per ICEA S-97-682 and UL Standard 1072.

Additional Standards:
•ICEA S-93-639
•NEMA WC74
•AEIC CS8
•Federal Specification J-C-30B

Note:
CT rating must be requested. CT ratings are available on sizes 1/0AWG and larger.