5kV UNISHIELDED 133% OR 100% – EPR – CPE

Specification:
HW204
Power Cable – Unishield
5KV/8KV UL Type MV-105, 105°C
Single Conductor, Shielded
EPR Insulation, CPE Jacket
5KV 133%, 8KV 100% Insulation Level
Copper Conductor

Catalog Number Size AWG/
kcmil
No. of Strands Insul Thickness Mils Jacket Thickness Mils Insul Diameter Inch Drain Wire Size AWG Cond. Diameter Inch Overall Diameter Inch Net Weight Lbs/Mft
HW204 00201 2 7 115 75 0.54 20 0.27 0.71 411
HW204 10101 1/0 19 115 75 0.62 20 0.34 0.79 563
HW204 20101 2/0 19 115 75 0.66 19 0.38 0.89 675
HW204 40101 4/0 19 115 80 0.76 19 0.48 0.94 961
HW204 25001 250 37 115 80 0.81 18 0.53 1.00 1122
HW204 35001 350 37 115 80 0.91 18 0.62 1.11 1476
HW204 50001 500 37 115 80 1.03 17 0.74 1.24 2015
HW204 75001 750 61 115 85 1.22 17 0.91 1.48 2893
HW204 10001 1000 61 115 100 1.38 16 1.06 1.61 3786

Application:
For use in power circuits up to 8KV when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for critical applications in harsh and caustic environments in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductor:
Compact soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-496, with a semi-conducting conductor shield.

Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682.

Shield:
Six (6) corrugated copper shield wires longitudinally embedded in an exterior semi-conducting CPE jacket per ICEA S-97-682.

Jacket:
Sunlight-resistant CPE per ICEA S-97-682 and UL Standard 1072.

Flame Tests:
•IEEE 383 70,000 BTU/hr flame test – CT-listed sizes 1/0AWG and larger
Additional Standards:
•ICEA S-93-639
•NEMA WC74
•AEIC CS8

Note:
CT rated on sizes 1/0 AWG and larger.