5kV/8kV 3-CONDUCTOR SHIELDED 133%/100% – EPR – PVC

Specification:
HW213
Power Cable
5KV/8KV UL Type MV-105, 105°C
Three Conductor, Shielded
EPR Insulation, PVC Jacket
5KV 133%, 8KV 100% Insulation Level
Copper Conductor

Catalog Number Size AWG/kcmil No. of Strands Insulation Thickness Mils Jacket Thickness Mils Insulation Diameter Inch Explosion Proof Connector UN Copper Grounding Condutor AWG Overall Diameter Inch Net Weight Lbs/Mft
HW213 00603 6 7 115 80 0.47 424UN05 6 1.38 1052
HW213 00403 4 7 115 80 0.52 424UN06 6 1.48 1265
HW213 00203 2 7 115 80 0.57 424UN06 6 1.61 1608
HW213 00103 1 19 115 110 0.61 424UN06 4 1.75 1989
HW213 10103 1/0 19 115 110 0.65 424UN07 4 1.84 2257
HW213 20103 2/0 19 115 110 0.70 424UN07 4 1.93 2609
HW213 30103 3/0 19 115 110 0.75 424UN07 3 2.04 3073
HW213 40103 4/0 19 115 110 0.80 424UN08 3 2.16 3598
HW213 25003 250 37 115 110 0.86 424UN08 3 2.30 4094
HW213 35003 350 37 115 110 0.96 424UN08 2 2.52 5288
HW213 50003 500 37 115 140 1.09 424UN09 1 2.89 7256
HW213 75003 750 61 115 140 1.28 - – - 1 3.77 10128

 
Application:
For use in primary power and distribution circuits up to 8KV when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.

Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682 with a semi-conducting insulation shield.

Shield:
Uncoated copper tape with a minimum 12.5% overlap per ICEA S-97-682.

Grounding Conductor:
Compressed soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance to UL Standard 1072.

Jacket:
Sunlight-resistant PVC per ICEA S-97-682 and UL Standard 1072.

Flame Tests:
UL and IEEE 383 70,000 BTU/hr flame test – CT-listed sizes 1/0AWG and larger.

Color Code:
ICEA Method 4

Additional Standards:
•ICEA S-93-639
•NEMA WC74
•AEIC CS8
•Federal Specification J-C-30B

Connectors:
Explosion Proof, Class I, Division 2: 424UN series ? aluminum exterior components, nickel-plated brass interior components

Note:
CT rating must be requested. CT ratings are available on all sizes.