C-L-X OKOSEAL TYPE P-OS THERMOCOUPLE 300V, RATED 105C, Sun Res

CONSTRUCTION:
Solid thermocouple alloys, Okoseal insulation, ASA/ISA color coded, twisted into one pair aluminum/polyester shield and coated stranded copper drain wire, rip cord, inner flame retardant Okoseal jacket, corrugated aluminum C-L-X sheath, overall Okoseal jacket.

SIZES:
#16 AWG

APPLICATION:
Okonite Type C-L-X P-OX (Pair/Triad-Overall Shield) Thermocouple Extension cables are designed for use as instrumentation and process control cables in ITC non-classified or labeled circuits up to 150 volts and 5 amps (750VA) and in Class 2 or 3 Power-Limited circuits where shielding against external interference is required, but shielding against interference among groups is not required; indoors or outdoors; in wet or dry location with conductor operating temperatures up to 105C; in cable trays; in raceways; supported by a messenger wire; under raised floors; for direct burial. Suitable Class I, Division 2, Class II, Division 2, or Class III, Division 2 and Class I, Zone 2 hazardous locations. The C-L-X sheath provides phusical protection against mechanical damage. It may be installed in both exposed and concealed work, secured to supports not greater than 6 feet apart. Meets UL 1581, IEEE 383 and IEEE 1202 vertical tray flame test. Also, passes 210,000 BTU vertical flame tray test per ICEA T-29-520.

 300V C-L-X

ASA/ISA Type Catalog Number Conductor Size AWG (strands) Number of Pairs Insul. Thick-mils Inner Jacket Thick mils C-L-X O.D.-Inches Outer Jacket Thickness-mils Approx. O.D.-Inches Approx. Net Wt (lbs/M’)
KX 584-20-3401 16(1X) 1 15 35 0.43 50 0.54 128